SCD43 offers best-in-class accuracy of ±(30 ppm + 3 % m.v.) within the 400-5000 ppm range, meeting building standards such as ANSI/ASHRAE 62.1-2022 Draft Addendum d, California Title 24, RESET® grade B, and WELL Building Standard™ (WELL v2).
Features:
- Photoacoustic NDIR
- Fully calibrated and linearised output
- I 2C interface
- On-chip RH and temperature compensation
- Automatic self-calibration (ASC)
- Shock and stress resistant
- Dust and condensation resistant
- Compact dimensions: 10,1 x 10,1 x 6,5 mm
- SMD soldering, tape & reel package
- MSL 1
- CO2 accuracy: ±30 ppm ±3 % @ 400-5000 ppm
- Response time (τ63%): 60 s
- RH accuracy: ±6 % RH, typ.
- Operating RH range: 0-95 % RH
- Response time (τ63%): 90 s
- Temperature accuracy: ± 0,8 °C
- Response time (τ63%): 120 s
- Supply voltage:2,4-5,5 V
- Average current: 15 mA, typ., periodic measurement mode
- Operating temperature range:-10 to +60 °C
Product benefits:
- Ideal for commercial and residential HVAC applications:
- Air handling and heat recovery units
- Wall-mount and duct-mount CO2 sensors
- Air purifiers and conditioners
- Thermostats
- Air quality monitoring devices
- Air exchangers
Schedule a meeting to request a sample for your project
Need to test a component during development? Schedule a meeting with us to discuss your project and request a sample. Please provide a brief description of your project in the form below to help us prepare for our meeting.
Note: Samples are provided for development projects only, not for individual personal use.
Thank you for understanding.
¿Le gustan nuestros artículos? ¡No se pierda ninguno! No tiene que preocuparse de nada; nosotros dispondremos el envío por usted.